Occupancy-Based HVAC Control: Demand-Controlled Ventilation in Shopping Malls and Buildings

Occupancy-based HVAC control means running a building's air-conditioning and ventilation according to how many people are actually in a space, instead of running them the same way for every hour the building is open. At its core is adjusting the amount of outdoor air brought in, which building engineers call demand-controlled ventilation (DCV). For malls and buildings in a hot, humid climate like Thailand's, every bit of outdoor air brought in has to be cooled and dehumidified before it reaches the space. Bringing in more than the people inside need is energy spent for nothing in return. This article is written for building engineers and the people responsible for energy. It explains the principle, the ways to measure demand, the spaces that suit it, and what to check before you start.

Occupancy-Based HVAC: Demand-Controlled Ventilation Guide

Why Buildings Bring In More Outdoor Air Than They Use

Buildings need outdoor air to dilute carbon dioxide, odours and other contaminants indoors. How much they need depends on the number of people and the type of space. The problem is that most systems set a single outdoor-air rate based on design occupancy, usually the busiest period, and run at that rate all day.

Shopping malls see very different numbers of people at different times, such as a weekday morning versus a weekend evening. Meeting rooms, cinemas and function rooms sit almost empty most of the day, then fill up in bursts. When outdoor air is set for the busiest period, every quiet hour is an hour in which the building cools and dehumidifies air that nobody needs.

Note: in this article, "HVAC control" refers to a building's air-conditioning and ventilation systems, not to setting the temperature on a home air conditioner.

What Is Demand-Controlled Ventilation?

Demand-controlled ventilation adjusts the amount of outdoor air brought in to match the real demand of a space, which varies with the number of people in it at that moment, without going below the minimum that space must receive.

To keep it simple, think of outdoor-air demand in two parts.

Part What it dilutes Can it follow occupancy?
People-related part Carbon dioxide and other emissions from people Yes. This is the part DCV adjusts
Area-related part Emissions from materials, surfaces, furniture and equipment in the building No. It must be maintained even when nobody is there

The values of each part for each type of space must follow the ventilation requirements and standards that apply to the building, as set by the design engineer. This article does not give figures in place of those standards.

Worked example (hypothetical figures): A zone is designed for 1,000 people. On a weekday morning, 250 people are actually there. The people-related part drops to a quarter of its design value, while the area-related part stays the same. Total outdoor air therefore falls, but not to a quarter, because the area-related part remains. The real result in each building depends on the ratio of these two parts, actual occupancy and outdoor weather.

How to Measure Demand: Schedules, CO2 Sensors and People Counts

The system needs a signal that tells it how many people are in a space. There are three common approaches.

Method How it works Strengths Limitations
Time schedules Set outdoor air by the periods when you expect more or fewer people Works with existing systems, no extra devices Does not know real occupancy; on unusually busy days the air may not be enough
Carbon dioxide (CO2) sensors Measure CO2 in the space or the return duct and adjust air to hold a set level Measures an air-quality outcome directly CO2 rises later than people arrive; sensors need periodic calibration; placement matters a lot
People counts from counting sensors Count people in and out at zone entrances and calculate real-time occupancy Knows the head count as soon as people arrive; works in large open halls Must cover every entrance and exit of the zone; does not measure air quality directly

In practice, the last two work well together. People counts signal that demand is about to rise, so the system can respond before CO2 climbs. CO2 sensors then confirm that air quality really is at the intended level.

Why People Counts Help in Large Open Halls

Mall atriums and corridors are open spaces that connect to each other. Air from one zone flows into the next, and high ceilings slow down mixing. A CO2 reading from one point may not represent the whole zone. Counting people at zone entrances gives the occupancy of the entire zone regardless of how the air mixes. See how the sensors work in our article How 3D People-Counting Sensors Work

How People Counts Feed Into Control

A typical sequence for occupancy-based HVAC control looks like this:

  1. Count people in and out at every zone entrance to get real-time occupancy
  2. Send occupancy per zone to the building management system (BMS) through a data interface the system supports
  3. The control system calculates the outdoor air needed from occupancy and the zone minimum
  4. Adjust the equipment, such as outdoor-air dampers or the fan speed of fresh-air units
  5. Check with CO2 sensors that air quality stays at the set level
  6. Log and review energy use against occupancy on a regular cycle to fine-tune the settings

Building control systems differ in how well they accept outside data. Some older buildings need control upgrades first, so surveying the existing system is the first step. See how control systems and energy management systems differ in our article What Is an EMS, and How Does It Differ From a BEMS and BMS?

Which Spaces Suit Occupancy-Based HVAC Control?

DCV pays off most in spaces where occupancy swings widely and density is high at peak times.

Space type Suitability What to check
Cinemas, meeting rooms, function rooms Very suitable; occupancy rises and falls in clear sessions Adjust ahead of each session; use booking schedules as an input
Mall atriums and corridors Suitable; occupancy differs greatly between weekdays and weekends Count every zone entrance; check airflow between zones
Food courts Partly suitable Kitchen exhaust needs make-up air; outdoor air cannot drop below what the exhaust requires
Offices Suitable, especially floors that are not full every day Look at real floor-by-floor use; read more in our article on occupancy sensors in offices
Toilets, car parks, plant rooms Not a target for occupancy-based DCV They have their own ventilation requirements

Engineering Points to Check Before You Start

  1. Never go below the minimum. The area-related part must always be kept, even when the space is empty, and must meet the requirements that apply to the building
  2. Maintain building pressure. Buildings in hot, humid climates are usually kept at slightly higher pressure inside than outside, to stop hot, humid air leaking in through doors. Cut outdoor air so far that it no longer balances the exhaust, and humid air will leak in instead
  3. Watch humidity, not just temperature. Changing the airflow changes the dehumidification load on air-handling units, so check that space humidity stays where it should
  4. Purge before opening. Many buildings bring in outdoor air for a period before opening to flush out what built up overnight. This step is still needed even before anyone arrives
  5. Set a fallback for missing data. If the counting sensors or data link fail, the system should return to design values, not stay at a low setting
  6. Commission the system. Check that dampers, fans and sensors respond as designed before going live
  7. Let the design engineer and the system owner decide. Changing control sequences affects air quality, comfort and the safety of building users

How to Get Started

  1. Review current settings. How much outdoor air is each unit set to deliver, and does it run the same way all day?
  2. Pick a pilot zone where occupancy swings widely and the controls can be adjusted, such as a function room or an atrium with clear entrances
  3. Collect baseline data before changing anything: hourly occupancy, CO2, temperature, humidity and the energy use of the relevant equipment
  4. Design the control sequence with an engineer, setting minimums, maximums and fallback values for missing data
  5. Adjust, then measure, comparing before and after while correcting for differences in weather and occupancy
  6. Roll out to other zones once the pilot results are clear

If your building is a designated building under Thailand's energy conservation law, this measure can support the building's energy management work. Read about a designated building's duties in our article What Is a Designated Building and What Must It Do?, and about the role of the person responsible for energy in The Person Responsible for Energy in a Designated Building. For an overview of where malls use more electricity than they need, see Shopping Mall Electricity Costs: Where to Cut With Real Visitor Data

People Data and Energy Data From IMAS

IMAS provides both people data and energy data for shopping malls and buildings.

  • 3D people counting: ceiling-mounted, counting in and out directions separately and giving real-time occupancy without identifying anyone. Xovis sensors can send data out over several standard data protocols, and Xovis lists adjusting HVAC and energy use to occupancy as one of its building-management applications
  • Visitor forecasting: predicts visitor numbers ahead of time from visitor history, sales, seasonality and weather, to help plan equipment operation on days when crowds are expected
  • AI building energy management: with Saturn Pyro on the IoTWatt 4.0 platform, it connects to existing meters and building control systems, analyses equipment such as chillers and air-conditioning systems, flags abnormal consumption, and tracks corrective work until it is closed

Feeding occupancy into a particular building's control system requires a survey of the existing system before design. The data shows which zones to adjust first; decisions on ventilation settings still belong to the building engineers who know the equipment limits and the building's users best. See the overview on our commercial building solutions page

Frequently asked questions

−What is occupancy-based HVAC control?

It means running air-conditioning and ventilation according to how many people are actually in a space, especially by adjusting the amount of outdoor air brought in, instead of running at one fixed rate all day.

+How is demand-controlled ventilation different from on/off schedules?

Schedules use expected time periods. Demand-controlled ventilation uses real signals from the space, such as people counts or CO2 levels, so it responds both on days with fewer people and on days with more than usual.

+Are CO2 sensors alone enough?

They work in rooms where air mixes well, but CO2 rises later than people arrive, and a single reading may not represent a large open hall. Combining people counts with CO2 lets the system respond quickly while still checking air quality.

+Will occupancy-based HVAC control make air quality worse?

It should not, as long as it is designed never to go below the space's minimum, has a fallback for missing data and is checked with CO2 sensors. The approach only cuts outdoor air brought in beyond what is needed.

+How much can it save?

That depends on the climate, the existing systems, the share of outdoor air and how much occupancy varies in your building. The most reliable figure is the result measured in a pilot zone in your own building.

Want to know how much more outdoor air your building brings in than its real occupancy needs?

The IMAS team can survey counting points, meters and building control systems, then put occupancy data and energy data side by side for your engineering team to base decisions on. Details and costs are given in the quotation.

Request an assessment of your building · See AI building energy management