The energy management report is the name people in the industry use for the report that the owner of a designated building in Thailand must submit every year to the Department of Alternative Energy Development and Efficiency (DEDE). Its full name under the Ministerial Regulation is the "report on the audit and certification of energy management". Energy officers at many shopping malls, office buildings, hotels and hospitals spend the end of the year and the start of the next on this work. This article summarises which provisions the report comes from, when it is due, what work each stage of the year involves, what data to prepare, and how this work connects to the ISO 50001 standard, so that building teams can plan the whole year in one rhythm.

What Is the Energy Management Report, and Who Must Submit It
Clause 11 of the Ministerial Regulation Prescribing Standards, Criteria and Procedures for Energy Management in Designated Factories and Designated Buildings B.E. 2552 (2009) (called the Energy Management Ministerial Regulation in this article) requires the owner of a designated building to submit to the Director-General a report on the audit and certification of energy management for the preceding year. The report is therefore a summary of the energy management work the building has done throughout the year, not a document written separately from the real work.
The party responsible for submitting is the owner of the designated building. Section 3 of the Energy Conservation Promotion Act B.E. 2535 (1992) defines this to include other persons who occupy the building. Whether a building is a designated building is determined by Section 3 of the Royal Decree Prescribing Designated Buildings B.E. 2538 (1995), which has two criteria. Meeting either one makes the building a designated building:
- The building has been approved by the electricity distributor to use an electricity meter, or to install a combined transformer, of 1,000 kilowatts or 1,175 kilovolt-amperes or more.
- Total energy use in the previous calendar year was equivalent to 20 million megajoules or more of electrical energy.
Both criteria count a single building, or several buildings under the same house number, together.
In day-to-day work, the person who collects the data and coordinates is usually the energy officer. The Ministerial Regulation on Qualifications, Duties and Number of Energy Responsible Persons B.E. 2552 (2009), Clause 3, sets out 4 duties, one of which is to assist the building owner with energy management under the Energy Management Ministerial Regulation.
Deadline for the Annual Energy Management Report
| Topic | What the Ministerial Regulation requires | Source |
|---|---|---|
| Report to be submitted | Report on the audit and certification of energy management for the preceding year | Energy Management Ministerial Regulation B.E. 2552 (2009), Clause 11 |
| Submitted to | Director-General of the Department of Alternative Energy Development and Efficiency | Clause 11 |
| When | Within March of every year | Clause 11 |
| First-year case | If the period of energy management up to 31 December is less than 180 days, submit the report for that period within March of the following year | Clause 11 |
| What it must pass before submission | Audit and certification of energy management by an auditor and certifier | Clause 10 |
Under the Regulation, an auditor and certifier is a person authorised to audit and certify energy management under the energy conservation promotion law. Section 48/1 of the Act allows the Director-General to authorise a person or juristic person to act in place of the competent officials.
In practice, there are two steps to complete before the end of March: the building team summarises the previous year's results, and then the auditor and certifier carries out the audit. The building team should book the auditor and certifier in advance and should close the December energy data early, to leave time to answer questions and add supporting evidence before submission.
What Is the Energy Management Report e-form?
The term e-form, which energy officers often search for, refers to filling in and submitting the report through an electronic channel. In practice, DEDE accepts reports through the department's electronic service system. The forms, system names and login steps may change from year to year, so building teams should check the latest forms and channel with DEDE every year before they start filling in, and should not rely on the previous year's file as a template without re-checking it.
The 8 Steps of Energy Management
Clause 3 of the Energy Management Ministerial Regulation requires the owner of a designated building to arrange energy management, which includes preparing an energy conservation policy, energy conservation targets and plans, and energy management methods. DEDE's published materials summarise this work as "8 steps", an ordering intended to make it easier to understand. The provisions to cite are Clauses 3 to 9 of the Ministerial Regulation.
| Step | What must be done, in brief | Source in the Ministerial Regulation | Data or evidence to prepare (good practice) |
|---|---|---|---|
| 1. Set up an energy management working group | Define the structure, authority and responsibilities, put them in a document and communicate it to personnel | Clause 5 | Appointment order, working group chart, evidence of communication |
| 2. Assess the initial status of energy management | Done when energy management methods are first adopted, before setting the policy | Clause 3, second paragraph | Assessment results and records of past energy work |
| 3. Set the energy conservation policy | Put it in a document signed by the building owner, with the details required by Clause 4, and communicate it to personnel | Clause 4 | Signed policy, evidence of posting or distribution |
| 4. Assess energy conservation potential | Audit and assess significant energy use, following the criteria and methods announced by the Minister | Clause 6 | Electricity use data by system, such as air conditioning, lighting and lifts |
| 5. Set energy conservation targets and plans | Set as a percentage of previous energy use, or as energy use per unit of output; specify the period, investment and expected results, together with a training plan and promotional activities | Clause 7 | Energy-use baseline, list of measures, training plan |
| 6. Carry out the plan, then monitor and analyse | Supervise the work according to the plan, and monitor and analyse performance against the targets and plans | Clause 8 | Records of measures implemented, before and after measurements |
| 7. Follow up and evaluate energy management | Done regularly, at least once a year | Clause 9 | Internal audit report |
| 8. Review, analyse and correct deficiencies | Done regularly, at least once a year | Clause 9 | Review meeting minutes and a list of corrections made |
At the end of the year, all of this work is audited and certified under Clause 10, and then the report is submitted under Clause 11. The right-hand column of the table is the author's suggested practice, not a list of documents required by law. For the documents that actually have to be attached, follow DEDE's latest form.
Planning the Year to Submit by March
The law requires only that the report be submitted within March every year, and that follow-up and review take place at least once a year. How the work is divided across the year is for each building to decide. In practice, building teams should spread the work across the year instead of bunching it at the start of the year, as follows.
- Early in the year: summarise the previous year's data, have the auditor and certifier carry out the audit, and submit the report within March.
- After submitting the report: use the observations from the audit to adjust the current year's targets and plan.
- During the year: carry out the measures in the plan, collect before and after measurements for each measure, and compare energy use with the targets every month.
- Late in the year: carry out the internal follow-up, hold a review meeting with management, and check that the documents for each step are complete.
A building that collects energy data continuously throughout the year can spend the start of the year reading results and planning, rather than chasing electricity bills and meter records retrospectively.
What Is ISO 50001?
ISO 50001 is an international standard of the International Organization for Standardization on energy management systems (EnMS). The word "system" here means an organisation's management system, not software or equipment. It is a voluntary standard: an organisation chooses to adopt it to manage energy systematically, and may choose to seek certification from a certification body.
The main elements of a system under this standard are:
- An energy policy set by top management, who are accountable for it
- An energy review to see what the organisation uses energy for and which parts are significant energy uses
- An energy baseline to compare later results against
- Energy performance indicators, such as energy per floor area or energy per building occupant
- Objectives, targets and action plans
- Internal audit
- Management review
All of these run in a cycle of plan, do, check and act (Plan-Do-Check-Act) so that energy performance keeps improving. For the details of each requirement, read the text of the edition of the standard your organisation uses.
How the Energy Management Report Relates to ISO 50001
Placing the work under the Ministerial Regulation next to the elements of ISO 50001 shows that both run in the same kind of cycle. The table below is the author's conceptual comparison, to help building teams see which pieces of work can be shared. It does not mean the requirements on the two sides are equal in every respect.
| Work under the Energy Management Ministerial Regulation B.E. 2552 (2009) | Closest element in ISO 50001 | Stage of the cycle |
|---|---|---|
| Energy management working group (Clause 5) | Energy management team and the role of top management | Plan |
| Energy conservation policy (Clause 4) | Energy policy | Plan |
| Initial status assessment and potential assessment (Clauses 3 and 6) | Energy review, energy baseline and indicators | Plan |
| Energy conservation targets and plans, training plan (Clause 7) | Objectives, targets, action plans and the competence of personnel | Plan |
| Carry out the plan, monitor and analyse (Clause 8) | Operational control, monitoring, measurement and analysis | Do and Check |
| Follow-up and evaluation (Clause 9) | Internal audit | Check |
| Review, analyse and correct deficiencies (Clause 9) | Management review and continual improvement | Act |
| Audit and certification by the auditor and certifier, then report submission (Clauses 10 and 11) | Certification audit by a certification body (only for organisations that choose to seek certification) | External verification |
Differences That Should Be Kept Separate
| Aspect | Energy management report under Thai law | ISO 50001 |
|---|---|---|
| Nature | A legal duty of the owner of a designated building | An international standard that an organisation adopts voluntarily |
| Who audits | The auditor and certifier under the energy conservation promotion law | A management system certification body |
| Output | A report submitted to the Director-General within March every year | An energy management system certificate, for organisations that seek certification |
| Scope | Each individual designated building | Defined by the organisation; may be one building or several |
In practice, a building certified to ISO 50001 should assume that its duty to submit the report under the Ministerial Regulation still applies in full. A building that completes every step under the Ministerial Regulation must still go through a certification body's process if it wants an ISO 50001 certificate. What can be shared is the same set of data and evidence, such as energy use by system, baselines, measure records, and records of follow-up and review meetings. A building that already works to the Ministerial Regulation routinely has a good foundation for building up to ISO 50001.
Data to Keep Throughout the Year

The same data can be used both for the report under the Ministerial Regulation and for an ISO 50001 system. In practice, a building team should keep at least the following:
- Monthly electricity units for every meter under the same house number, and other energy types if any
- Electricity use by system, such as air conditioning, chilled-water plant, lighting, lifts and escalators, to assess significant energy use
- Variables that explain energy use, such as opening hours, floor area in use, outdoor temperature and the number of building occupants
- Records of measures: what was done, when, who was responsible, with before and after measurements
- Records of training and energy conservation promotion activities
- Records of follow-up and review meetings
For shopping malls and office buildings, the number of people in the building is a variable that helps explain why energy use differs from month to month. You can read more on this idea in the article Shopping Mall Electricity Costs: Where to Save When You Know the Real Headcount.
Where a Building Energy Management System Helps with Reporting
A Building Energy Management System collects data continuously from meters and building control systems, so the data needed at each step is available throughout the year. The differences between EMS, BEMS and BMS are covered in the article What Is a Building EMS?
IMAS, together with Saturn Pyro, provides an AI-based building energy management system on the IoTWatt 4.0 platform, delivered as a continuously running digital energy audit (Digital Energy Audit as a Service), for commercial buildings, shopping malls and airports. Data from the system helps prepare for the report as follows:
- Continuous energy-use data from electricity meters, building control systems, supervisory control and data acquisition (SCADA) systems and the IoT devices the building already has, used to support potential assessment and baseline setting
- Energy-audit-style findings from real data, analysed with AI and machine learning down to equipment level, such as chillers, pumps and air-conditioning systems
- Alerts when energy use departs from normal, or when peak electricity demand rises
- Tracking of corrective actions: assigning an owner, keeping evidence and following status until the item is closed, which can serve as a record of measures
- Savings records split into savings available, savings achieved and savings missed, together with data for management review meetings
This data helps building teams prepare reports faster and with a traceable record, but the system does not fill in DEDE's forms on the building team's behalf. The AI in the system is a tool that helps engineers read data and make decisions. Certifying the data in the report, and the legal responsibility, remain with the building owner, the energy officer and the auditor and certifier as the law provides.
Frequently asked questions
−When must the energy management report be submitted?
Clause 11 of the Energy Management Ministerial Regulation B.E. 2552 (2009) requires the report on the audit and certification of energy management for the preceding year to be submitted to the Director-General within March of every year. If, in the first year, the period of energy management up to 31 December is less than 180 days, the report for that period must be submitted within March of the following year.
+Who is the auditor and certifier of energy management?
The auditor and certifier is a person authorised to audit and certify energy management under the energy conservation promotion law, being a person or juristic person authorised by the Director-General under Section 48/1 of the Act. Building teams can check the list of authorised parties with DEDE.
+Is the "8 steps" of energy management written in the law?
The term "8 steps" is a summary used in DEDE's published materials. The content of each step comes from Clauses 3 to 9 of the Energy Management Ministerial Regulation B.E. 2552 (2009). When citing in organisational documents, cite the clause numbers of the Ministerial Regulation.
+If we have ISO 50001, do we still have to submit the energy management report?
ISO 50001 is a voluntary standard, while submitting the report is a duty of the owner of a designated building under the Ministerial Regulation. In practice, treat them as two things done side by side, which can use the same data and evidence. If you need clarity for a specific case, ask DEDE.
+Can a building energy management system complete the report for us?
The system helps collect and summarise the data needed, such as energy use by system, results of measures and the status of corrective actions. Filling in DEDE's forms, the audit and certification, and signing remain the work of the building team, the auditor and certifier, and the building owner.
Want your building's energy data ready all year?
The IMAS team can survey the meters and systems your building already has, plan the connections and start from a pilot building or system. Details and costs are provided in a quotation.
Talk to the IMAS team · See the AI-based building energy management system
The legal information in this article is cited from the texts as checked on 17 November B.E. 2569 (2026). Laws and forms may be amended afterwards. Before making any decision on legal compliance, check with the Department of Alternative Energy Development and Efficiency or the building's legal adviser.
References
- Energy Conservation Promotion Act B.E. 2535 (1992), as amended by the Energy Conservation Promotion Act (No. 2) B.E. 2550 (2007) (Government Gazette Vol. 109, Part 33 A, and Vol. 124, Part 87 A)
- Royal Decree Prescribing Designated Buildings B.E. 2538 (1995) (Government Gazette, Council of State edition, Vol. 112, Part 33 A)
- Ministerial Regulation Prescribing Standards, Criteria and Procedures for Energy Management in Designated Factories and Designated Buildings B.E. 2552 (2009) (Government Gazette Vol. 126, Part 47 A)
- Ministerial Regulation on Qualifications, Duties and Number of Energy Responsible Persons B.E. 2552 (2009) (Government Gazette Vol. 126, Part 49 A)
- Department of Alternative Energy Development and Efficiency. Presentation document, Guidelines for Driving Energy Savings (B.E. 2565 / 2022), on the 8-step energy management
- International Organization for Standardization. ISO 50001: Energy management systems — Requirements with guidance for use.
- Saturn Pyro Sdn Bhd. IoTWatt 4.0 Digital Energy Audit as a Service. Website: saturnpyro.com